Skip to Content

AC/DC, True, RMS, FC, wireless, clamp, meter,, 1000, A, +, iFlex

  • Mõõdab vahelduvvoolu kaasasoleva 18-tollise või 36-tollise iFlex vooluanduriga
  • VFD madalpääsfilter mittelineaarsete signaalide täpseks mõõtmiseks
  • Kaugjuhtimisega logimine, trendide jälgimine ja seire, et tuvastada ajutised rikked
  • Sisselülitusvoolu mõõtmine müra filtreerimiseks ja käivitusvoolu registreerimiseks
Specifications: Fluke 376 FC True-RMS Clamp Meter with iFlex
General Specifications
AC Current via Jaw
Range999.9 A
Resolution 0.1 A
Accuracy 2% ±5 digits (10 Hz to 100 Hz)
2.5% ±5 digits (100-500 Hz)
Crest Factor (50 Hz/60 Hz)3 @ 500 A
2.5 @ 600 A
Add 2% for C.F. >2
AC Current via Flexible Current Probe
Range2500 A
Resolution0.1 A (≤ 600 A)
1 A (≤ 2500 A)
Accuracy3% ±5 digits (5 – 500 Hz)
Crest Factor (50/60Hz)3.0 at 1100 A
2.5 at 1400 A
1.42 at 2500 A
Add 2% for C.F. > 2
Flexible current probe
i2500-10 Flexi2500-18 Flexi2500-36 Flex
A
Distance from Optimum0.5 in (12.7 mm)1.4 in (35.6 mm)4.8 in (122.2 mm)
Error±0.5 %±0.5 %±0.5 %
B
Distance from Optimum0.8 in (20.3 mm)2.0 in (50.8 mm)5.3 in (133.6 mm)
Error±1.0 %±1.0 %±1.0 %
C
Distance from Optimum1.4 in (35.6 mm)2.5 in (63.5 mm)5.8 in (147.6 mm)
Error±2.0 %±2.0 %±2.0 %
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
DC Current
Range999.9 A
Resolution0.1 A
Accuracy2% ±5 digits
AC Voltage
Range1000 V
Resolution0.1 V (≤600.0 V)
1 V (≤1000 V)
Accuracy1% ±5 digits (20 Hz to 500 Hz)
DC Voltage
Range1000 V
Resolution0.1 V (≤600.0 V)
1 V (≤1000 V)
Accuracy1% ±5 digits
mV dc
Range500.0 mV
Resolution0.1 mV
Accuracy1% ±5 digits
Frequency via Jaw
Range5.0 Hz to 500.0 Hz
Resolution 0.1 Hz
Accuracy 0.5% ±5 digits
Trigger level 5 Hz to 10 Hz, ≥10 A
10 Hz to 100 Hz, ≥5 A
100 Hz to 500 Hz, ≥10 A
Frequency via Flexible Current Probe
Range5.0 Hz to 500.0 Hz
Resolution 0.1 Hz
Accuracy 0.5% ±5 digits
Trigger level 5 Hz to 20 Hz, ≥25 A
20 Hz to 100 Hz, ≥20 A
100 Hz to 500 Hz, ≥25 A
Resistance
Range60 kΩ
Resolution0.1 Ω (≤600 Ω)
1 Ω (≤6000 Ω)
10 Ω (≤60 kΩ)
Accuracy1% ±5 digits
Capacitance
Range1000 μF
Resolution0.1 μF (≤ 100 μF)
1 μ F (≤ 1000 μF)
Accuracy1% ±4 digits
Mechanical Specifications
Maximum voltage between any terminal and earth ground1000 V
Batteries2 AA, NEDA 15A, IEC LR6
Operating temperature-10 °C to +50 °C
Storage temperature-40 °C to +60 °C
Operating humidity -
non-condensing (< 10°C)
≤90% RH (at 10 °C to 30 °C)
≤75% RH (at 30 °C to 40 °C)
≤45% RH (at 40 °C to 50 °C)
Operating altitude2000 m
Storage altitude12,000 m
Size (L x W x H)249 x 85 x 45 mm
Weight395 g
Jaw opening34 mm
775.00 € 775.00 € (Tax excluded)


Manufacturer Part Number: FLUKE-376, FC
Internal Reference: EE-100-176-088